dc.descriptionFull text access from Treasures at UT Dallas is restricted to current UTD affiliates (use the provided Link to Article).
dc.description.abstractWe propose a novel contactless measurement technique for detecting the phasing of double overhead transmission lines which are used to supply power to a transformer in the substation. Different from traditional contactless methods whose sensors should be quite close to measured overhead lines, the proposed method uses a electric field (EF) sensor located on the ground to measure the ground-level electric field distribution. Then, the remote contactless phasing test method can be realized based on the distribution waveform. The proposed method has been validated by experimental tests on a reduced scale model of double overhead transmission lines.
dc.language.isoen
dc.publisherInstitute of Electrical and Electronics Engineers Inc.
dc.relation.urihttp://dx.doi.org/10.1109/IGBSG.2018.8393516
dc.rights©2018 IEEE
dc.subjectElectric fields
dc.subjectOverhead electric lines
dc.subjectDetectors
dc.titleHigh-voltage Phasing Test Using A Contactless Sensor
dc.type.genrearticle
dc.description.departmentErik Jonsson School of Engineering and Computer Science
dc.identifier.bibliographicCitationMa, X., K. -L Chen, X. Yang, and Y. Guo. 2018. "High-voltage phasing test using a contactless sensor." International Conference on Intelligent Green Building and Smart Grid: 1-3, doi:10.1109/IGBSG.2018.8393516
dc.source.journalInternational Conference on Intelligent Green Building and Smart Grid